Datasheet ADE9000 (Analog Devices) - 15

FabricanteAnalog Devices
DescripciónHigh Performance, Multiphase Energy, and Power Quality Measurement IC
Páginas / Página72 / 15 — Data Sheet. ADE9000. ENERGY ERROR OVER FREQUENCY AND POWER FACTOR. 0.10. …
RevisiónA
Formato / tamaño de archivoPDF / 1.1 Mb
Idioma del documentoInglés

Data Sheet. ADE9000. ENERGY ERROR OVER FREQUENCY AND POWER FACTOR. 0.10. POWER FACTOR = +1 POWER FACTOR = +0.5. POWER FACTOR = +1

Data Sheet ADE9000 ENERGY ERROR OVER FREQUENCY AND POWER FACTOR 0.10 POWER FACTOR = +1 POWER FACTOR = +0.5 POWER FACTOR = +1

Línea de modelo para esta hoja de datos

Versión de texto del documento

Data Sheet ADE9000 ENERGY ERROR OVER FREQUENCY AND POWER FACTOR
Total energies obtained from a sinusoidal voltage with an amplitude of 50% of ful scale, a sinusoidal current with a constant amplitude of 10% of full scale, a variable frequency between 45 Hz and 65 Hz, and the integrator off. Fundamental energies obtained with a fundamental voltage component, with an amplitude of 50% of full scale in phase with the fifth harmonic, a current with a 50 Hz component that has constant amplitude of 10% of ful scale, a fifth harmonic with a constant amplitude of 40% of fundamental, and the integrator off, unless otherwise noted.
0.10 0.10 POWER FACTOR = +1 POWER FACTOR = +0.5 POWER FACTOR = +1 POWER FACTOR = –0.5 POWER FACTOR = +0.5 POWER FACTOR = –0.5 0.05 0.05 %) %) R ( 0 R ( 0 RRO RRO E E –0.05 –0.05 –0.10 –0.10
13 15
40 45 50 55 60 65 70
1
40 45 50 55 60 65 70
1
LINE FREQUENCY (Hz)
15210-
LINE FREQUENCY (Hz)
15210- Figure 16. Total Active Energy Error vs. Line Frequency, Figure 19. Fundamental Active Energy Error vs. Line Frequency, Power Factor = −0.5, Power Factor = +0.5, and Power Factor = +1 Power Factor = −0.5, Power Factor = +0.5, and Power Factor = +1
0.10 0.10 POWER FACTOR = 0 POWER FACTOR = 0 POWER FACTOR = +0.866 POWER FACTOR = +0.866 POWER FACTOR = –0.866 POWER FACTOR = –0.866 0.05 0.05 %) %) R ( 0 R ( 0 RRO RRO E E –0.05 –0.05 –0.10 –0.10
14 16
40 45 50 55 60 65 70
1
40 45 50 55 60 65 70
1
LINE FREQUENCY (Hz)
15210-
LINE FREQUENCY (Hz)
15210- Figure 17. Total Reactive Energy Error vs. Line Frequency, Figure 20. Fundamental Reactive Energy Error vs. Line Frequency, Power Factor = −0.866, Power Factor = 0, and Power Factor = +0.866 Power Factor = −0.866, Power Factor = 0, and Power Factor = +0.866
0.10 0.10 0.05 0.05 %) %) R ( 0 R ( 0 RRO RRO E E –0.05 –0.05 –0.1 –0.10
17
40 45 50 55 60 65 70
150
40 45 50 55 60 65 70
1
LINE FREQUENCY (Hz)
15210-
LINE FREQUENCY (Hz)
15210- Figure 18. Total Apparent Energy Error vs. Line Frequency Figure 21. Fundamental Apparent Energy Error vs. Line Frequency Rev. A | Page 15 of 72 Document Outline FEATURES APPLICATIONS GENERAL DESCRIPTION REVISION HISTORY TYPICAL APPLICATIONS CIRCUIT SPECIFICATIONS TIMING CHARACTERISTICS ABSOLUTE MAXIMUM RATINGS THERMAL RESISTANCE ESD CAUTION PIN CONFIGURATION AND FUNCTION DESCRIPTIONS TYPICAL PERFORMANCE CHARACTERISTICS ENERGY LINEARITY OVER SUPPLY AND TEMPERATURE ENERGY ERROR OVER FREQUENCY AND POWER FACTOR ENERGY LINEARITY REPEATABILITY RMS LINEARITY OVER TEMPERATURE AND RMS ERROR OVER FREQUENCY ENERGY AND RMS LINEARITY WITH INTEGRATOR ON ENERGY AND RMS ERROR OVER FREQUENCY WITH INTEGRATOR ON SIGNAL-TO-NOISE RATIO PERFORMANCE TEST CIRCUIT TERMINOLOGY THEORY OF OPERATION MEASUREMENTS Current Channel ADC_REDIRECT Multiplexer Current Channel Gain, xIGAIN IB Calculation Using ICONSEL High-Pass Filter Digital Integrator Phase Compensation Multipoint Phase and Gain Calibration Voltage Channel RMS and Power Measurements Total and Fundamental RMS Total and Fundamental Active Power Total and Fundamental Reactive Power Total and Fundamental Apparent Power No Load Detection, Energy Accumulation, and Power Accumulation Features No Load Detection Feature Energy Accumulation Power Accumulation Digital to Frequency Conversion—CFx Output Energy and Phase Selection Configuring the CFx Pulse Width CFx Pulse Sign Clearing the CFx Accumulator POWER QUALITY MEASUREMENTS Zero-Crossing Detection CF3/ZX Zero-Crossing Timeout Line Period Calculation Angle Measurement Phase Sequence Error Detection Fast RMS½ Measurement 10 Cycle RMS/12 Cycle RMS Dip and Swell Indication Overcurrent Indication Peak Detection Power Factor Total Harmonic Distortion (THD) Resampling 128 Points per Cycle Temperature WAVEFORM BUFFER INTERRUPTS/EVENTS ACCESSING ON-CHIP DATA SPI PROTOCOL OVERVIEW ADDITIONAL COMMUNICATION VERIFICATION REGISTERS CRC OF CONFIGURATION REGISTERS CONFIGURATION LOCK REGISTER MAP REGISTER DETAILS OUTLINE DIMENSIONS ORDERING GUIDE